PV-94129B
Revised 04-00
Catalog Section 55
(00-02-0126)
Pneumatic Valves for
Fuel Gas Shutoff
Models M2582-P
and M5180-P
■
Pneumatically Open and Shut Off Fuel Gas
Automatically or Semi-automatically
■
■
Pneumatic Control Pressure Can Be
Air, Gas or Oil
Models for 2 in. or 1 in. (51 mm or
25 mm) Fuel Gas Lines
MURPHY
MATIC
Model M2582-P
®
bar] and fully opens the seat at 3 psi (21 kPa) Control Pressure (Maximum):
Description
[.21 bar]. The valve can be manually opened
with lever and latched against inlet pressure
of 100 psi (689 kPa) [6.89 bar]. The latch will
release after pilot pressure reaches 2.5 psi (17
kPa) [.17 bar].
M2582-P: 75 psi (517 kPa) [5.17 bar]
The M2582-P and M5180-P are pneumatical-
ly controlled fuel shut-off valves that open
and close automatically or semi-automatical-
ly. The pneumatic control pressure can be air,
oil or gas. A manual lever aids in opening the
valve when control pressure is insufficient. A
gas escape vent, when properly vented and
maintained, releases trapped gas from the
valve after shutoff.
M5180-P: 80 psig (552 kPa) [5.52 bar]
How to Order
To order, use the diagram below.
Specifications
Valve Body: Sandcast aluminum
(alodined for corrosion resistance).
Optional steel body available on M5180-P
models only (see How to Order).
______ – __
Model
Basic Operation
Automatic: As the control pressure/vacuum
increases the valve will open. When the control
pressure/vacuum decreases, the valve will close.
M2582-P
M5180-P
Valve Seat: Buna-N
Valve Inlet Pressure (Maximum):
M2582-P: 80 psi (552 kPa) [5.52 bar]
M5180-P: 100 psi (689 kPa) [6.89 bar]
Semi-Automatic: If the control pressure/vacuum
is too low and the valve does not open automat-
ically, it can be opened manually by lifting the
built-in lever arm and setting the latch. The
latch resets automatically when control pressure
rises enough to release it.
Body
Blank = Aluminum
2 = Steel (applies to M5180-P)
Parts Exposed to Gas Line Flow:
M2582-P:
• Aluminum
Warranty
• Buna-N
M2582-P is for 1 in. (25 mm) gas lines. It auto-
matically opens at 2 psi (14 kPa) [.14 bar] and
fully opens the seat at 3 psi (21 kPa) [.21 bar].
The valve can be manually opened with the
lever and latch against inlet pressure of 80 psi
(552 kPa) [5.52 bar]. The latch will release after
pilot pressure reaches 2.5 psi (17 kPa) [.17 bar].
A limited warranty on materials and workmanship
is given with this FW Murphy product. A copy of
the warranty may be viewed or printed by going to
• 302, 303, and 17-7 PH stainless steel
M5180-P:
• Aluminum (Steel optional)
• Buna-N
• 302, 303, 304, and 416 stainless steel
Control Diaphragm: Flexweave polyester
fabric and Buna-N elastomer.
The M5180-P is for 2 in. (52 mm) gas lines.
It automatically opens at 2 psi (14 kPa) [.14
|
Lexmark 3200 User Manual
Panasonic Kx Fp101 User Manual
Ricoh Aficio Cl7000 Mf User Manual
Samsung Sf 5100 User Manual
Silva Battery Charger Solar I User Manual
Soleus Air Air Conditioner Gb Ttw 14 User Manual
Sony Found Not Kdl 46w4100 User Manual
Trane Air Conditioner 61e User Manual
Whynter Air Conditioner Arc 143mx User Manual
Xerox C424 User Manual